TOYOPUC
TOYOPUC-PC2J/3J AS-i M module
1.Feature
1.It is a master module in accordance with AS-i(Actuator Sensor Interface).
2.The data of 124 points of input/124 points of output can be exchanged with the 31 slaves or less.
3.The network wiring length is 100m or less.
4.The cycle time of AS-i is 5ms or less.
5.The slave connection is one-touch because of a special cable.
6.Connected form of network is free.
※AS-i is a cereal ministry wiring system which integrated the signal line with the power supply line. |
|
 |
2. Specification
(1)Communication specification
| Item |
Content |
| I/O number |
124 points of input/124 points of output
(4 points of input/4 points of output per one slave) |
| Communication area |
I/O relay(X/Y000 - 7FF)
Link relay(L000 - 7FF)
Internal relay(M000 - 7FF) |
| Number of slaves |
31 or less |
| The total extension of cable |
100m or less
(It is possible to extend up to 300m by the repeater. ) |
| Cycle time |
5ms or less(31 slave) |
| Cable |
Two line type(There is no shield. ) |
| Connected form |
Free tree structure for bus to diverge free |
| Transmission speed |
156kbps |
| Data transmission method |
Master/slave(polling) |
| Power-supply unit |
Power supply only for ASi |
(1)Module specification
| Item |
Content |
| Form |
THU-5503(AS-i M) |
| I/O module allocation point |
0 points |
| I/O module kind identification code |
B8
(It is the same as a high-speed remote I/O master.) |
| Link parameter |
Setting of the header address of communication
(Set by a high-speed remote I/O master. ) |
| The number of sheets of the maximum mounting |
8 pieces
(Other link modules include . ) |
| Mounting position |
It is possible to mount on all slots of a basic(CPU) base and the extension base . |
| Consumption memory capacity |
4Kbyte |
3.Composition
|