1.function.
|
1.In/Out short circuit detection
I/O power current is monitored. A short circuit is detected when detects more than 50mA per 1 point. |
| |
|
|
|
2.Wire cutting detection
I/O power current is monitored. A wire-cutting is detected when less than 0.3mA per 1 input point. |
| |
|
|
|
3.I/O power voltage monitoring
Whether I/O power is supplied to units or not is reported to a Master.
|
| |
|
|
4.Diagnostic information collection
Diagnostic information of short circuit, wire-cutting and I/O power down can be read via message communication.
Trouble shooting time is much reduced using these information for facility information display. J-DLINK-M2,PC3JG and PC3JG-P have Message communication available masters.
|
 |
| |
|
|
2. General specifications
| Item |
Specifications |
| Communication power |
DC11-25V
(supplied through a communication connector) |
| Ambient temperature (usage) |
-10-55 degrees centigrade |
| Ambient temperature (preservation) |
-25-65 degrees centigrade |
| Relative humidity |
25-85%RH (No condensation allowed) |
| Atomosphere |
No corrosive gas allowed |
| Vibration resistance |
JIS C0911 conformity (150m/s2 3 directions 3 times each) |
Freq. |
Acce. |
Ampl. |
Scan |
| 10~60Hz |
- |
0.35mm |
10 times
(1 octave/1 min.) |
| 60~150Hz |
50m/s2 |
- |
| Shock resistance |
JIS C0912 conformity (150m/s23 directions 3 times each) |
| Noise resistance |
IEC 61000-4-4 conformity 2kV (Power line) |
| Insulation resistance |
20Mohm (by DC250V meggar) Charge circuit, non-charge circuit. |
| Insulation resistance |
Comunication power
(includeing internal power supplies) |
| I/O type |
Current consumption |
| DRMT-32/00 |
Less than 65mA |
| DRMT-00/32 |
Less than 55mA |
| DRMT-16/16 |
Less than 60mA |
| DRMT-32/00P |
Less than 65mA |
| DRMT-00/32P |
Less than 55mA |
| DRMT-16/16P |
Less than 60mA |
| Installation |
DIN35mm rail installation |
| Installation strength |
50N (except for rail directions), 10N (rail direction) |
| External dimentions |
245(W)×50(H)×56.4(D)mm |
| Weight |
Less than 0.48kg |
| 保護装置 |
IP20 |
3.Series
| Item |
Code |
Input |
Output |
Polarity |
| DRMT-32/00P |
TFU-6110 |
32 point |
0 point |
PNP |
| DRMT-00/32P |
TFU-6111 |
0 point |
32 point |
| DRMT-16/16P |
TFU-6112 |
16 point |
16 point |
| DRMT-32/00 |
TFU-6120 |
32 point |
0 point |
NPN |
| DRMT-00/32 |
TFU-6121 |
0 point |
32 point |
| DRMT-16/16 |
TFU-6122 |
16 point |
16 point |
4.Input specifications
| Item |
Specifications |
| Insulation method |
Photo coupler insulation |
| Rated input voltage |
DC24V |
| Rated input current |
Less than 6.0mA/point |
| Usable voltage range |
DC20.4~26.4V(DC24V -15~+10%) |
| ON voltage/current |
More than DC15V/3mA |
NPN:between each input terminal and +V |
| PPNP:between each input terminal and 0V |
| OFF voltage/current |
Less than DC5V/1mA |
NPN:between each input terminal and +V |
| PNP:between each input terminal and 0V |
| Input resistance |
About 4k ohm |
| Time |
OFF → ON |
Less than 1.5ms |
| ON → OFF |
Less than 1.5ms |
| Input points per a common |
16 points/common |
| Operation display |
I/O lamp display (yellow) |
| I/O power short circuit detection |
Detection at more than 50mA/point |
| No connenction detection |
Detection at more than 0.3mA/point |
| Connection status |
Screw-less terminal block (green) |
5.Output specifications
| Item |
Specifications |
| Insulation method |
Photo coupler insulation |
| Rated load voltage |
DC24V |
| Max. load current |
0.5A/point、4.0A/common |
| Usable voltage range |
DC20.4~26.4V(DC24V-15~+10%) |
| Max. voltage descend at ON |
Less than 1.2V |
NPN:between each output terminal and 0V |
| NPN:between each output terminal and V |
| Leak current at OFF |
Less than 0.3mA *1 |
NPN:between each output terminal and 0V |
| NPN:between each output terminal and V |
| Time |
OFF → ON |
Less than 0.5ms |
| ON → OFF |
Less than 1.5ms |
| Output points per a common |
16 points/common |
| Operation display |
I/O lamp display (yellow) |
| No connection detection |
Detection at less than 3mA/point |
| Connection status |
Screw-less terminal block (red) |
| Output at communication error |
All points OFF |
*1 : If a connected load works under 0.3mA, please add bleeder resister.
|