产品信息

TOYOPUC 系列

TOYOPUC DRMT 系列

The DRMT series is DeviceNet compatible Remote I/O terminal with input /output wiring short circuit or wire-cutting detection  

1.function.

1.In/Out short circuit detection
I/O power current is monitored. A short circuit is detected when detects more than 50mA per 1 point.
     
2.Wire cutting detection
I/O power current is monitored. A wire-cutting is detected when less than 0.3mA per 1 input point.
     
3.I/O power voltage monitoring
Whether I/O power is supplied to units or not is reported to a Master.
     
4.Diagnostic information collection
Diagnostic information of short circuit, wire-cutting and I/O power down can be read via message communication. Trouble shooting time is much reduced using these information for facility information display. J-DLINK-M2,PC3JG and PC3JG-P have Message communication available masters.
     

2. General specifications

Item Specifications
Communication power DC11-25V (supplied through a communication connector)
Ambient temperature (usage) -10-55 degrees centigrade
Ambient temperature (preservation) -25-65 degrees centigrade
Relative humidity 25-85%RH (No condensation allowed)
Atomosphere No corrosive gas allowed
Vibration resistance JIS C0911 conformity
(150m/s2 3 directions 3 times each)
Freq. Acce. Ampl. Scan
10~60Hz - 0.35mm 10 times (1 octave/1 min.)
60~150Hz 50m/s2 -
Shock resistance JIS C0912 conformity (150m/s23 directions 3 times each)
Noise resistance IEC 61000-4-4 conformity 2kV (Power line)
Insulation resistance 20Mohm (by DC250V meggar) Charge circuit, non-charge circuit.
Insulation resistance Comunication power (includeing internal power supplies)
I/O type Current consumption
DRMT-32/00 Less than 65mA
DRMT-00/32 Less than 55mA
DRMT-16/16 Less than 60mA
DRMT-32/00P Less than 65mA
DRMT-00/32P Less than 55mA
DRMT-16/16P Less than 60mA
Installation DIN35mm rail installation
Installation strength 50N (except for rail directions), 10N (rail direction)
External dimentions 245(W)×50(H)×56.4(D)mm
Weight Less than 0.48kg
保護装置 IP20

3.Series

Item Code Input Output Polarity
DRMT-32/00P TFU-6110 32 point 0 point PNP
DRMT-00/32P TFU-6111 0 point 32 point
DRMT-16/16P TFU-6112 16 point 16 point
DRMT-32/00 TFU-6120 32 point 0 point NPN
DRMT-00/32 TFU-6121 0 point 32 point
DRMT-16/16 TFU-6122 16 point 16 point

4.Input specifications

Item Specifications
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current Less than 6.0mA/point
Usable voltage range DC20.4~26.4V(DC24V -15~+10%)
ON voltage/current More than DC15V/3mA NPN:between each input terminal and +V
PPNP:between each input terminal and 0V
OFF voltage/current Less than DC5V/1mA NPN:between each input terminal and +V
PNP:between each input terminal and 0V
Input resistance About 4k ohm
Time OFF → ON Less than 1.5ms
ON → OFF Less than 1.5ms
Input points per a common 16 points/common
Operation display I/O lamp display (yellow)
I/O power short circuit detection Detection at more than 50mA/point
No connenction detection Detection at more than 0.3mA/point
Connection status Screw-less terminal block (green)

5.Output specifications

Item Specifications
Insulation method Photo coupler insulation
Rated load voltage DC24V
Max. load current 0.5A/point、4.0A/common
Usable voltage range DC20.4~26.4V(DC24V-15~+10%)
Max. voltage descend at ON Less than 1.2V NPN:between each output terminal and 0V
NPN:between each output terminal and V
Leak current at OFF Less than 0.3mA *1 NPN:between each output terminal and 0V
NPN:between each output terminal and V
Time OFF → ON Less than 0.5ms
ON → OFF Less than 1.5ms
Output points per a common 16 points/common
Operation display I/O lamp display (yellow)
No connection detection Detection at less than 3mA/point
Connection status Screw-less terminal block (red)
Output at communication error All points OFF


*1 : If a connected load works under 0.3mA, please add bleeder resister.