TOYOPUC
DeviceNet DLNK series
1.Master
 |
|
 |
| The F-DLNK-M is the master module for the TOYOPUC-PCF/FS. |
|
The J-DLNK-M is the master module for the TOYOPUC-PC3J/2J. |
●DLNK communication specification
| Item |
specification |
| Baudrate |
500k/250k/125kbps |
| Maximum connection node |
64 units(1 master,63 slave units) |
| I/O points |
Max. 2048 points |
| I/O allocation |
8-point increment,8 points minimum |
| Communication area |
X,Y,L,M,EX,EY,EL,EM, |
| Communication distance |
Baudrate |
Total distance |
Branch line length |
Total Branch line length |
| 500kbps |
Below 100m |
Below 6m |
Below 39m |
| 250kbps |
Below 250m |
Below 6m |
Below 78m |
| 125kbps |
Below 500m |
Below 6m |
Below 156m |
2. Slave
●DLNK-S (enviroment durable I/O block)
 |
|
IP66 achieved
IP66 has been achieved by use of cast aluminum housing. This enables the module to be directly connected to the equipment,eliminating the necessity for a realy terminal box
Comprehensively eliminated wiring work
Wiring work load has been reduced greatly by using connectors for all connections including I/O,communication lines and power lines.Wiring work does not require any tools.
Two I/O for one connector
Pair operatons such as advance and retract can be handled with one connector.
Power supply for inputs is possible
Power can be supplied externally for input devices that require a large current such as a 3-line sensor.
External power supply for I/O is not required. (Only DLNK-ST,DLNK-SP 16/00 and -SPH 16/00) |
Large lineup to chose from
| DLNK-S 8/8 |
input 8 points,output 8 points |
| DLNK-S 16/00 |
input 16 points |
| DLNK-S 00/16 |
output 16 points |
| DLNK-S 8/0 |
input 8 points |
| DLNK-S 0/8 |
output 8 points |
| DLNK-ST 16/00 |
input 16 points |
Unit that needs no external
power supply for I/O |
| DLNK-ST 8/0 |
input 8 points |
| DLNK-SP 16/00 |
input 16 points |
Communication connector is
a pre-wired cable unit. |
| DLNK-SP 8/8 |
input 8 points,output 8 points |
| DLNK-SP 00/16 |
output 16 points |
| DLNK-SPH 16/00 |
input 16 points |
2-wire I/O dedicated
communication connector
is a pre-wired cable unit. |
| DLNK-SPH 8/8 |
input 8 points,output 8 points |
| DLNK-SPH 00/16 |
output 16 points |
| Input specification |
|
output specification |
| Item |
Specification |
| Rated input voltage |
DC24V |
| Rated input current |
7mA |
| Insulation method |
Photo coupler insulation |
| I/O common type |
NPN |
|
|
| Item |
Specification |
| Rated output voltage |
DC24V |
| Maximum output current |
0.3 A / point, 1.2 A / common |
| Insulation method |
Photo coupler insulation |
| I/O common type |
NPN |
|
| |
●DLNK Terminal
 |
|
The DLNK terminal is a slave module that uses connector terminal block for I/O connection.
Large lineup to chose from
The following are available for DLNK terminals.
- DLNK Terminal 32/32 32-point input/
32-point output
- DLNK Terminal 40/24 40-point input/
24-point output
- DLNK Terminal 00/64 64-point output
- DLNK Terminal 8/8 8-point input/
8-point output
- DLNK Terminal 16/0 16-point input
- DLNK Terminal 0/16 16-point output
|
| 64-point type |
|
16-point type |
| |
●J-DLNK-S
 |
|
An abundant I/O modules are available,which are mounted on the PC3J/PC2J base.
Large lineup of I/O modules
Being able to use a large number of I/O modules of PC3J/PC2J enables you to select any kinds of actuator and sensors(24VDC,100VAC) as widely as you like. J-DLNK-S2 can perform I/O data exchange among CPUs. |
| |
3.PLC
●PC2FS-3D
 |
|
DeviceNet. The PC2FS-3D is a PLC that contains a DeviceNet Master module.
Standard DLNK-M
DLNK,PC link and Computer link are equipped as standard communication modules.
Link 0:Computer link
Link 1:PC link
Link 2:DLNK
32-point input/ 32-point output
|
4.List of module
| Device |
Name |
Type |
Specifications |
DLNK-M (Master) |
J-DLNK-M |
THK-5398 |
The master module for the TOYOPUC- PC3J/2J |
Maximum connection node: 63 units
I/O points: Max. 2048 points
Baudrate: 500/250/125kbps |
| F-DLNK-M |
TFU-5359 |
The master module for the TOYOPUC- PC2F/FS |
| PC2FS-3D |
TSC-5401 |
PLC that contains a DeviceNet Master module |
| PC3JD |
TIC-5642 |
PLC that contains a DeviceNet Master module |
| Wiring-saved unit
DLNK-S
(Slave) |
DLNK-S 8/8 |
TFU-5445 |
input 8 points/ output 8 points |
Rated input current: 7mA/ point
Maximum output current: 0.3A/point
1.2A/common |
| DLNK-S 16/00 |
TFU-5459 |
input 16 points |
| DLNK-S 00/16 |
TFU-5460 |
output 16 points |
| DLNK-S 8/0 |
TFU-5461 |
input 8 points |
| DLNK-S 0/8 |
TFU-5462 |
output 8 points |
| DLNK-ST 16/00 |
TFU-5711 |
input 16 points |
Unit that needs no external power supply for I/O. |
| DLNK-ST 8/0 |
TFU-5712 |
input 8 points |
| DLNK-ST 16/00(+) |
TFU-5814 |
input 16 points, PNP type |
| DLNK-ST 8/0(+) |
TFU-5815 |
input 8 points, PNP type |
| DLNK-SP 16/00 |
TFU-5731 |
input 16 points |
Communication connector is
a pre-wired cable unit. |
| DLNK-SP 8/8 |
TFU-5732 |
input 8 points/ output 8 points |
| DLNK-SP 00/16 |
TFU-5733 |
output 16 points |
| DLNK-SPH 16/00 |
TFU-5787 |
input 16 points |
2-wire I/O dedicated
communication connector
is a pre-wired cable unit. |
| DLNK-SPH 8/8 |
TFU-5788 |
input 8 points/ output 8 points |
| DLNK-SPH 00/16 |
TFU-5789 |
output 16 points |
| DLNK-1S 8/0P |
TFU-5756 |
input 8 points, PNP type, one input for one connector |
| DLNK-1S 0/8P |
TFU-5847 |
output 8 points, PNP type, one input for one connector |
DLNK TERMINAL
(Slave) |
DLNK TERMINAL 40/24 |
TFU-5423 |
40-point input/ 24-point output |
Rated input current: 7mA/point
Maximum output current: 0.3A/point,2A/common |
| DLNK TERMINAL 32/32 |
TFU-5424 |
32-point input/ 32-point output |
| DLNK TERMINAL 00/64 |
TFU-5425 |
64-point output |
| DLNK TERMINAL 8/8 |
TFU-5440 |
8-point input/ 8-point output |
Input current: 7mA/point,Max. output current: 0.5A/point,2A/common |
| DLNK TERMINAL 16/0 |
TFU-5442 |
16-point input |
Input current: 7mA/point |
| DLNK TERMINAL 0/16 |
TFU-5834 |
16-point output |
Max. output current :0.5A/point,4A/common |
| DLNK TERMINAL 24/16 |
TFU-5777 |
24-point input/ 16-point output |
Input current: 5mA/point,Max. output current: 50mA/point,0.8A/common |
| Slave modules
for the PC3J/PC2J |
J-DLNK-S |
THU-5441 |
Max512points 500/250/125kbps (I/O terminal type) |
| J-DLNK-S2 |
THU-5563 |
Max512points 500/250/125kbps (between-PC link type) |
*1: Varies according to selection for user-memory allocation.
*2: Support for PC3J mode only
*3: 4-line communication possible when only port 1 is used.
*4: When initial settings (no link parameters) are in effect, operation is as a standard-specification computer link.
*5: Use of Hellowin is required.

|
|
|